- Power Quality Solutions
- Power Quality Measurement Solutions
- Condition Base Monitoring Solutions
- Energy Efficiency Solutions
C-10-01, Oasis Square,
Jalan PJU 1A/7A,
Ara Damansara,
47301 Petaling Jaya,
Selangor, Malaysia.
PQE Power Quality Analyzer (G4000 series)
PQE Power Quality Analyzer G4400 Series is the best PQ analyzer in the market today as it is equipped with the revolutionary PQZIP patent algorithm for continuous waveform recording. This most advanced analyzer enables you to predict, prevent and troubleshoot an incidence easily, without the need to set any trigger or threshold in order to capture a specific event.
FEATURES
PQZIP inside
- Continuous waveform recording
- Trigger free setup
- 5,000 power parameters @ 1/2 cycle resolution
- Easy deployment
Class A
Far surpassing the highest standards set by the industry, the BLACKBOX device series complies with standards for: aggregations, time clock uncertainty, flagging, and transient influence quantities.
Superior Accuracy
PQE’s pioneering measurement method utilizes a dual-range gain of 2 x 16 Bit to yield, a superior accuracy far surpassing IEC 61000-4-30 Class A requirements, thereby capturing the finest details & deviations in Power Quality parameters.
Synchronized Monitoring
A unique time synchronization algorithm assures that logged data from multiple units is synchronized & displayed on the same time scale with typical 0.1 ms resolution. Every event on a grid is accurately analyzed for precise root cause analysis, behaviour propagation, and traced to its source
- Continuous waveform recording
- Trigger free setup
- 5,000 power parameters @ 1/2 cycle resolution
- Easy deployment
APPLICATIONS
Utilities (transmission, distribution, generation)
- Optimizes protective equipment configuration and substation automation solutions
- Ensures a reliable and consistent supply of energy
- Evaluates the performance of breakers and relays
- Identifies and manage peak demand
- Real time power quality monitoring to meet any international standard
- Produces detailed & comprehensive statistical records
Energy consumer (critical power, industrial, commercial, etc.)
- Measures and analyzes system efficiency, provides solutions and increases profits
- Negotiates capabilities with power providers
- Detects electric bill inconsistencies
- Avoids power quality compliance issues
- Monitors and analyze power quality in real time
SPECIFICATIONS
Product Series |
G4410 |
G4420 |
G4430 |
---|---|---|---|
Voltage Sampling Rate, Maximum Samples/Cycle |
256 |
512 |
1,024 |
Voltage Harmonics (Individual, Even, Odd, Total) Up to – |
127TH |
255th |
511th |
Type of Analog to Digital Converter |
16/201 bit |
16/201 bit |
16/201 bit |
Internal Memory |
128 MB |
4 GB |
16 GB |
Transient Detection, Microseconds (50Hz/60Hz) |
78.1/65.1μs |
39/32.5μs |
19.5/16.3μs |
Ethernet Ports |
1 |
2 |
2 |
Power Over Ethernet (PoE- Out) |
– |
1 |
1 |
Voltage Ride Through on Power Loss (up to) |
10 sec. |
25 sec. |
25 sec. |
Applicable Measurement Standards |
EN50160, IEEE1159, IEEE519, IEC61000-4-15,IEC61000-4-7, IEC61000-4-30 Class A,IEC62053-22/23 Class 0.2 |
||
Applicable EMC Standards |
EN55011 Group 1 Class A, EN61000-6-2, IEC60255EN60439-1 (clauses 7.9.1, 7.9.3, 7.9.4, 7.10.3, 7.10.4),FCC Part 15 Subpart B Class A, IEC61000-3-3 |
||
Voltage Channels |
|||
Channels |
3 Phase + Neutral |
||
Nominal Full Scale |
1,000V |
||
Maximum Peak Measurement |
8kV |
||
Input Impedance |
3MΩ |
||
Uncertainty |
0.1% of Nominal |
||
Current Channels |
|||
Channels |
3 Phase + Neutral |
||
Nominal Full Scale |
5A |
||
Maximum Peak Measurement |
50A |
||
Burden |
0.0001VA@5A |
||
Phase |
±0.42°@3A ±0.17°@5A |
||
Uncertainty |
0.1% of Nominal |
||
Frequency Measurement |
|||
Fundamental Frequency |
42.5 Hz to 69 Hz |
||
Frequency Resolution |
10 mHz |
||
Frequency Accuracy |
±10 mHz |
||
Physical |
|||
Dimensions |
175mm x 232mm x138mm |
||
Weight |
1.7Kg |
||
Power Supply |
|||
Operating Range |
100-260 VAC: 50/60 Hz 100-300 VDC |
||
Auxiliary DC Supply |
48 VDC |
||
Auxiliary Supply – PoE In |
PoE In According to 802.3af |
||
Time Synchronization |
|||
Real Time Clock |
20ppm |
||
GPS |
100-200μs |
||
IRIG B |
100-200μs |
||
SNTP Server |
50-100μs |
||
DCF-77 |
±15ms |
||
Environmental Conditions |
|||
Operation Temperature |
-20°C to 70°C(-4°F to 158°F) |
||
Storage Temperature |
-40°C to 85°C(-40°F to 185°F) |
For all your power quality monitoring needs, contact us today and discover the latest solutions on offer. Our experienced team can guide you in selecting the best solution for your requirements and assist you in every step of the way. Don't let power quality issues impair your systems - get in touch with us now to learn how we can help!